SAMSUNG ELECTRONICSSAMSUNGDV MTMAir ConditionerSAMSUNG DVM Air ConditionerTe chnical Manual DVM E-D/B(cover)-E<03759 3/21/02 6:48 PM Page 1
I11(9) Space SavingThe outdoor units connected with several indoor units do not require much space.1) Conventional System2) DVM System DVM E-D/B(chapt
III. Indoor unit4. Capacity tableIII40Unit SizeOutdoor temperature(ºC, DB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW10121416182021232527
III41Unit SizeOutdoor temperature(ºC, DB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW10121416182021232527293133353739101214161820212325272
III. Indoor unit4. Capacity tableIII42Unit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-303579111315-15-12-10
III43Unit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-303579111315-15-12-10-7-5-303579111315-15-12-10-7-5-30
III. Indoor unit4. Capacity tableIII44TC : Total capacityUnit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-30
III45Unit SizeOutdoor temperature(ºC, WB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW10121416182021232527293133353739101214161820212325272
III. Indoor unit4. Capacity tableIII46Unit SizeOutdoor temperature(ºC, WB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW10121416182021232527
III47Unit SizeOutdoor temperature(ºC, WB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW10121416182021232527293133353739101214161820212325272
III. Indoor unit4. Capacity tableIII48(2) HeatingUnit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-3035791113
III49Unit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-303579111315-15-12-10-7-5-303579111315-15-12-10-7-5-30
I12I. Overview1. DVM system series25%50%75%100%ABABABAB25%50%75%100%73448016119971301515857169961720019007713863137353648675046626763068021.1341.7942.
III. Indoor unit4. Capacity tableIII50Unit SizeOutdoor temperature(ºC)16.0TCkW18.0TCkW20.0TCkW22.0TCkW24.0TCkWDB WB-15-12-10-7-5-303579111315-14-13-11
III515. Dimension5-1. 1-way cassette typeUnit : mm◆ Check the position of remote control sensor and indicators before installing the unit.◆ If you wan
III. Indoor unit5. DimensionIII525-2. 4-way cassette type(1) 5.2kW ~ 7.2kWUnit : mm◆ Check the position of remote control sensor and indicators before
III53(2) 10.5kWUnit : mm◆ Check the position of remote control sensor and indicators before installing the unit.◆ If you want to install optional part
III. Indoor unit5. DimensionIII545-3. Duct type (Low silhouette)Unit : mm◆ If you want to install optional parts, refer to an appropriate installation
III555-4. Duct type (Built-in)(1) 2.0kW ~ 4.0kWUnit : mm◆ If you want to install optional parts, refer to an appropriate installation manual. DVM E-D/
III. Indoor unit5. DimensionIII56(2) 5.2kW ~ 7.2kWUnit : mm◆ If you want to install optional parts, refer to an appropriate installation manual. DVM E
III575-5. Duct type (High pressure)Unit : mm◆ If you want to install optional parts, refer to an appropriate installation manual. DVM E-D/B(chapter3-2
III. Indoor unit5. DimensionIII585-6. Wall-Mounted type(1) 2.0kW ~ 4.0kWUnit : mm◆ If you want to install optional parts, refer to an appropriate inst
III59(2) 5.2kW ~ 7.2kWUnit : mm◆ If you want to install optional parts, refer to an appropriate installation manual. DVM E-D/B(chapter3-2)-E<03759
I13(2) DVM test condition(3) VAV test condition❋ The static pressure is equal to the maximum open position by adjusting the damper.#1 (5.2kW) #2 (5.2k
III. Indoor unit5. DimensionIII605-7. Floor standing type1850mm312mm1016mm600mm330mmUnit : mm◆ If you want to install optional parts, refer to an appr
III615-8. Ceiling typeUnit : mm DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 61
III. Indoor unit5. DimensionIII625-9. Wireless remote controller / Receiver(1) For 1-way cassette / 4-way cassette / Wall-mounted / Floor standing / C
III63◆ AVMKC✻MGKC118IE0MGKC118IM0MGKC118IA0MGKC118IC0◆ AVMKH✻MGKH118IE0MGKH118IM0MGKH118IA0MGKH118IC0Fan indicatorFilter sign indicatorRemote control
III. Indoor unit5. DimensionIII64◆ AVMCC✻MGCC095IE0MGCC095IM0MGCC095IA0MGCC095IC0◆ AVMCH✻MGCH095IE0MGCH095IM0MGCH095IA0MGCH095IC0On/off buttonFan indi
III65◆ AVMWC✻◆ AVMWH✻Remote control sensorFilter sign indicatorFan indicatorTimer indicatorOn/off indicatorOn/off buttonRemote control sensorFilter si
III. Indoor unit5. DimensionIII66◆ AVMPC✻◆ AVMPH✻On/off button Turbo buttonOperating modeselection buttonTemperatureadjustment buttonFan speed adjustm
III67◆ AVMFC✻◆ AVMFH✻ DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 67
III. Indoor unit5. DimensionIII68(2) For duct type (AVMD✻/ AVMB✻/ AVMH✻)◆ MR-AC00◆ MR-AH00 DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 68
III69◆ MRK-B00(concealed type)◆ MRW-10A(wire kit)◆ MRK-A00(standard type)◆ MRW-10A(wire kit) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 6
③②I14I. Overview2. DVM line-up2-1. Numbering system of model(1) Indoor unit and outdoor unit (Conventional model)①Semi-finished product②Classification
III. Indoor unit5. DimensionIII705-10. Wired remote controller(1) For 1-way cassette / 4-way cassette / Wall-mounted / Floor standing / Ceiling type(A
III71(2) For duct type (AVMD✻/ AVMB✻/ AVMH✻)◆ MWR-AC00◆ MWR-AH00Wiring holeWiring hole DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 71
III. Indoor unit5. DimensionIII725-11. Option controller(1) Centralized controller(2) Function controllerWiring hole DVM E-D/B(chapter3-2)-E<03759
III736. Refrigerant system diagram(Cooling only & heat pump)6-1. Refrigerant system diagram6-2. Main parts status(1) Temperature sensor (EIS, Evap
III. Indoor unit7. Electric circuit diagramIII747-1. 1-way cassette type(1) Cooling only (AVMKC✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM P
III75(2) Heat pump (AVMKH✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 75
III. Indoor unit7. Electric circuit diagramIII767-2. 4-way cassette type(1) Cooling only (AVMCC✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM P
III77(2) Heat pump (AVMCH✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 77
III. Indoor unit7. Electric circuit diagramIII787-3. Duct type(1) Cooling only (AVMDC✻/ AVMBC✻/ AVMHC✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37
III79(2) Heat pump (AVMDH✻/ AVMBH✻/ AVMHH✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 79
I15(2) Indoor unit and outdoor unit (New Model) 1) Indoor unit①Semi-finished product② Classification of productAVM①K②H③100④B⑤A⑥0⑦Model1-way 4-way 2-wa
III. Indoor unit7. Electric circuit diagramIII807-4. Wall-mounted type(1) Cooling only (AVMWC✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Pag
III81(2) Heat pump (AVMWH✻) DVM E-D/B(chapter3-2)-E<03759 3/21/02 7:37 PM Page 81
III. Indoor unit7. Electric circuit diagramIII827-5. Floor standing type(1) Cooling only (AVMPC✻) DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM P
III83(2) Heat pump (AVMPH✻) DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 83
III. Indoor unit7. Electric circuit diagramIII847-6. Ceiling type(1) Cooling only (AVMFC✻) DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 84
III85(2) Heat pump (AVMFH✻) DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 85
III. Indoor unit8. Noise levelIII868-1. Overall◆ 1-way cassette type1m1mMicrophoneModel230V/50Hz 220V/60HzHigh32.036.038.0✻✻020✻✻✻✻026/032✻✻✻✻035/040✻
III87✻✻020✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC-
III. Indoor unit8. Noise levelIII88✻✻035/040✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-6
III89✻✻052✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC-
I16I. Overview2. DVM line-up2) Outdoor unit①Semi-finished product⑥Combination of indoor unit RVM①H②060③B④A⑤A⑥0⑦Model②Mode③Capacity (HP x 10, 3 digits
III. Indoor unit8. Noise levelIII90✻✻105✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-
III91✻✻052✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC-
III. Indoor unit8. Noise levelIII92✻✻020✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-
III93✻✻035/040✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-3
III. Indoor unit8. Noise levelIII94✻✻070/072✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-6
III95✻✻105✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC-
III. Indoor unit8. Noise levelIII96✻✻020✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-
III97✻✻035/040✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-3
III. Indoor unit8. Noise levelIII98✻✻070/072✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-6
III99✻✻060✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC-
I17(3) OptionsParts Model Example● MEV-14SA● MEV-18SA● MEV-24SAMEV : Optional electronic expansion valve①: Electronic expansion valve model (2 digits)
III. Indoor unit8. Noise levelIII100✻✻082/083✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-
III101✻✻052✻✻Sound pressure level (dB, ref.2xE-5)70.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35NC
III. Indoor unit9. Velocity of air flow & temperature distributionIII1029-1. 1-way cassette type(1) AVMKH035✻1) Velocity of air flow2) Heating tem
III1039-2. 4-way cassette type(1) AVMCH070✻1) Velocity of air flow2) Heating temperature distribution ◆The standard ceiling height is 2.7 meters and t
III. Indoor unit9. Velocity of air flow & temperature distributionIII104(2) AVMCH105✻1) Velocity of air flow2) Heating temperature distribution◆Th
III1059-3. Wall-mounted type(1) AVMWH035✻1) Velocity of air flow2) Heating temperature distribution ◆The standard ceiling height is 2.7 meters and tho
III. Indoor unit9. Velocity of air flow & temperature distributionIII106(2) AVMWH070✻1) Velocity of air flow2) Heating temperature distribution ◆T
III1079-4. Ceiling type(1) AVMFH070✻1) Velocity of air flow2) Heating temperature distribution◆The standard ceiling height is 2.7 meters and those val
III. Indoor unit10. Fan specificationsIII10810-1. Duct type (Low silhoutte)(1) ✻✻052✻✻(2) ✻✻070/072✻✻10-2. Duct type (Built-in)(1) ✻✻020✻✻(2) ✻✻026/03
III109(3) ✻✻035/040✻✻(4) ✻✻026/032✻✻External static pressure (mmAq)10911128765432106789101112LOWMIDHITURBOFan speed (m3/min)Limitation of min. air flo
I18I. Overview2. DVM line-upParts Model ExampleMRW : Optional receiver & display unit wire①: Length (m, 2 digits)②: VersionMRW- ①②Receiver& di
III. Indoor unit10. Fan specificationsIII11010-3. Duct type (High pressure)(1) ✻✻105✻✻(2) ✻✻128✻✻2015105020 25 30 35 40TURBOMIDLOWHI2015105020 25 30 3
III11111. Panel11-1. 1-way cassette type(1) Design(2) StatusItemCooling onlyHeat pumpModelMGKC118IE0MGKC118IM0MGKC118IA0MGKC118IC0MGKH118IE0MGKH118IM0
III. Indoor unit11. PanelIII112ItemCooling onlyHeat pumpModelMGCC095IE0MGCC095IM0MGCC095IA0MGCC095IC0MGCH095IE0MGCH095IM0MGCH095IA0MGCH095IC0LanguageE
III11312. Electronic expansion valve kit12-1. Design12-2. Status depending on the combinationABCItemMEV-14 MEV-18#1OO#2OO#3O#1 #2 #3OMXD14K300AMXD14K2
III. Indoor unit13. OptionsIII114ItemPanelOOOO------------Electronic expansion valvekitOOIntegratedIntegratedIntegratedIntegratedIntegratedIntegratedI
III115ItemDrainpump----MDP-075SAMDP-075SAMDP-075SAMDP-075SAMDP-075SAMDP-075SA------WirelessremotecontrollerMR-AC01MR-AH01MR-AC01MR-AH01MR-AC00MR-AH00M
III116 DVM E-D/B(chapter3-3)-E<03759 3/21/02 7:38 PM Page 116
1. Selection of outdoor units(based on cooling load)2. Specification2-1. 50Hz2-2. 60Hz464. Capacity table4-1. 50Hz4-2. 60Hz14205. Dimension5-1
IV. Outdoor unit1. Unit selection (with cooling load)IV21-1. Indoor unit selectionSelect the nearest load capacity indoor unit with given load after f
IV3Room A2.4262.8Room B2.8262.8Room C3.2353.77Room D3.4353.77Room E4.8525.6Room F7.2707.54LocationLoad (kW)Unit sizeCapacity(kW)Room A2.4262.66Room B2
I19Parts Model ExampleStandard for model nameMSC : Super cooler①, ②: HP of applicable outdoor unit (marked as 00 if it is 10.0 HP)③: Power supplyB:220
IV. Outdoor unit2. SpecificationIV42-1. 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionRVMC060GAM0RVMC060GAM1RVMC060GDM0 RVMC100
IV5ModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionRVMH060GBM0 RVMH060GDM0 RVMH080GAM0RVMH100GAM0RVMH100GCM03, 380~415, 50Set55000(70
IV. Outdoor unit2. SpecificationIV62-2. 60HzCoolingHeatingCoolingCoolingHeatingModelTypePiston displacementOutputTypeOutputAir flow rateCoolingHeating
IV7CoolingHeatingCoolingCoolingHeatingModelTypePiston displacementOutputTypeOutputAir flow rateCoolingHeatingCoolingHeatingCoolingHeatingCoolingHeatin
IV. Outdoor unit3. Functional parts and safety devicesIV83-1. Outdoor unitItem Code NameRVMC050CBM0 RVMC060GDM0Motor outputCompressor safety OLPCrank
IV9Item Code NameMUF7201F1 RVMC100GAM0Motor outputCompressor safety OLPCrank case heaterFan motorSafety thermostatopen temp.trip currentmodeloutputono
IV. Outdoor unit3. Functional parts and safety devicesIV10Item Code NameRVMH050CBM0RVMH080GAM0RVMH060GDM0Motor outputCompressor safety OLPCrank case h
IV11Item Code NameMotor outputCompressor safety OLPCrank case heaterFan motorSafety thermostatHigh pressure switchLow pressure switchThermistor (disch
IV. Outdoor unit3. Functional parts and safety devicesIV12Item Code NameRVMH100GCM0Motor outputCompressor safety OLPCrank case heaterFan motorSafety t
IV133-2. Super coolerItem Code NameMUF7201F1 (SUB)Motor outputCompressor safety OLPCrank case heaterFan motorSafety thermostatHigh pressure switchLow
I20I. Overview2. DVM line-up2-2. Combination(1) Outdoor unit1) Cooling onlyMainSuper coolerDesignPower supply Model50Hz60Hz--380~415V, 3ø208~230V, 3øR
IV. Outdoor unit4. Capacity tableIV14Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV15Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW8.208.208.208.2
IV. Outdoor unit4. Capacity tableIV16Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV17Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW101214161820212
IV. Outdoor unit4. Capacity tableIV18Combination,%(Capacityindex)Outdoor temperature 16 18 20 21 22 24ºC, DB ºC, WBTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIk
IV192) ✻✻100✻✻TC : Total capacity, PI : Power inputCombination,%(Capacityindex)Outdoor temperature 16 18 20 21 22 24ºC, DB ºC, WBTCkWTCkWTCkWTCkWTCk
IV. Outdoor unit4. Capacity tableIV20Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV21Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW101214161820212
IV. Outdoor unit4. Capacity tableIV22Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV23Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW101214161820212
1. DVM system series1-1. What is DVM?1-2. Features of DVM 1-3. DVM vs VAV 67122. DVM line-up2-1. Numbering system ofmodel2-2. Combination1420IIOvervie
I21MainSuper coolerDesignMax. connectibleindoor unitsTotal capacity of indoorunits (kW, ISO standard)Supercooler87--Remark8810---O--For Middle EastFor
IV. Outdoor unit4. Capacity tableIV24Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV25Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW101214161820212
IV. Outdoor unit4. Capacity tableIV26Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPI
IV27Combination,%(Capacityindex)Outdoor temperature(ºC, DB)14 16 18 19 20 22 24TCkWTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIkWPIkWPIkWPIkWPIkW101214161820212
IV. Outdoor unit4. Capacity tableIV28Combination,%(Capacityindex)Outdoor temperature 16 18 20 21 22 24ºC, DB ºC, WBTCkWTCkWTCkWTCkWTCkWTCkWPIkWPIkWPIk
IV292) ✻✻060✻✻TC : Total capacity, PI : Power inputCombination,%(Capacityindex)Outdoor temperature 16 18 20 21 22 24ºC, DB ºC, WBTCkWTCkWTCkWTCkWTCk
IV. Outdoor unit4. Capacity tableIV303) ✻✻100✻✻TC : Total capacity, PI : Power inputCombination,%(Capacityindex)Outdoor temperature 16 18 20 21 22 2
IV315. Dimension5-1. Upward (2-FAN)Unit : mm DVM E-D/B(chapter4-1)-E<03759 3/21/02 7:39 PM Page 31
IV. Outdoor unit5. DimensionIV325-2. OnwardUnit : mm DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:39 PM Page 32
IV335-3. Upward (1-FAN)17651575Unit : mm DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 33
I22I. Overview2. DVM line-up2) Heat pumpMainSuper coolerDesignPower supply Model50Hz60Hz380~415V, 3ø380~415V, 3ø208~230V, 3øRVMH060GBM0RVMH060GDM0RVMH
IV. Outdoor unit5. DimensionIV345-4. Upward(Super cooler)Unit : mm DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 34
IV356. Refrigerant system diagram6-1. Cooling only(1) ✻✻050/060/072✻✻fanmotorsuper coolertemperaturesensortemperaturesensortemperature sensorheat exch
IV. Outdoor unit6. Refrigerant system diagramIV36(2) ✻✻080/100✻✻temperaturesensortemper-aturesensorfanmotortemperaturesensorcond outsensorheat exchang
IV37(3) Main parts status1) Digital scroll compressorThe variable capacity type compressor to control the capacity up to 10 ~ 100% with 19 steps. 2) A
IV. Outdoor unit6. Refrigerant system diagramIV386-2. Heat pump(1) ✻✻050/060✻✻fanmotortemperaturesensortemperaturesensorheat exchangerhigh pressureswi
IV39(2) ✻✻080/100✻✻fanmotortemperaturesensorcond outsensorheat exchangerhigh pressureswitch4-wayvalve(4-W/V)digital scroll com-pressor solenoidvalve (
IV. Outdoor unit6. Refrigerant system diagramIV40(3) Main parts status1) Digital scroll compressorThe variable capacity type compressor to control the
IV4111) Temperature sensor (OATS, Outdoor Air Temperature Sensor) To measure the outdoor temperature which is used for the determination of start meth
IV. Outdoor unit7. Electric circuit diagramIV427-1. Cooling only(1) ✻✻050/060/072✻✻ DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 42
IV43(2) ✻✻080/100✻✻ DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 43
I23MainSuper coolerDesignMax. connectibleindoor unitsTotal capacity of indoorunits (kW, ISO standard)Supercooler887---Remark11141414------For Middle E
IV. Outdoor unit7. Electric circuit diagramIV447-2. Heat pump(1) ✻✻050/060✻✻ DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 44
IV45(2) ✻✻080/100✻✻ DVM E-D/B(chapter4-2)-E<03759 3/21/02 7:40 PM Page 45
IV. Outdoor unit8. Consideration for outdoor unit selectionIV468-1. Change of capacity depending on refrigerant piping length(1) Change of cooling cap
IV478-2. Condition of operating restriction(1) Cooling(2) Heating(3) Cautions for characteristics of heating capacity DVM E-D/B(chapter4-2)-E<03759
IV. Outdoor unit9. Noise levelIV48✻✻035✻✻Sound pressure level (dB, ref.2xE-5)80.070.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65
IV49✻✻060✻✻Sound pressure level (dB, ref.2xE-5)80.070.060.050.040.030.020.010.00.063 125 250 500 1000 40002000 8000NC-65NC-60NC-55NC-50NC-45NC-40NC-35
IV. Outdoor unit10. OptionsIV50❋ The discharge duct shall be bought suitable for the quantities of Fan. Optional ItemsRefnet kitSVM-SNETCentralizedcon
1. Product1-1. Preparation for installation1-2. Deciding on where to install the air conditioner1-3. Space requirements for the air conditioner1-4.
V. Installation1. ProductV21-1. Preparation for installationWhen deciding on the location of the air conditioner with the owner, the following restric
V31-2. Deciding on where to install the air conditioner.(1) Indoor unit◆ There must be no obstacles near the air inlet and outlet.◆ Install the indoor
I24I. Overview1. System line-up(2) Indoor unitDesignPowersupply2.0kW(7000Btu/h)2.6kW(9000Btu/h)3.2kW(11000Btu/h)3.5kW(12000Btu/h)4.0kW(13500Btu/h)5.2k
V. Installation1. ProductV41-3. Space requirements for the air conditioner(1) Indoor unit1) 1-way cassette type2) 4-way cassette type3) Duct type (Low
V54) Duct type (Built-in)5) Duct type (High pressure)You must have 5mm or more space betweenthe ceiling and the bottom of indoor unit.Otherwise, the n
V. Installation1. ProductV67) Floor standing type8) Ceiling type DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 6
V7(2) Outdoor unit1) If there is no obstacle around the outdoor unit...2) If there is an obstacle around the outdoor unit...◆ If an obstacle in front
V. Installation1. ProductV81-4. Accessories(1) 1-way cassette typePattern sheet(1)Flexible hose(1)Insulationdrain hose (1)Installationmanual (1)Rubber
V9Pattern sheet(1)Insulation A(2)Insulation B(2)Drain Socket(1)Owner’sInstructions (1)InstallationManual (1)(4) Duct type (Built-in)Pattern sheet(1)In
V. Installation1. ProductV10(7) Floor standing type(6) Ceiling type DVM E-D/B(chapter5)-E<03759 3/21/02 7:40 PM Page 10
V111-5. Installation(1) Indoor unit (Example; 4-way cassette type)1) Place the pattern sheet on the ceiling at the spot where youwant to install the i
V. Installation1. ProductV12(2) Outdoor unitThe outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and
V132. Panel2-1. 1-way cassette type(1) Accessories(2) InstallationM4x12 tapped screw(6)M5x16 bolt (4)Wireless remotecontroller(1)Battery (2) STS 2S-2x
I25DesignPowersupply7.0kW(24000Btu/h)7.2kW(24000Btu/h)8.2kW(28000Btu/h)8.3kW(28000Btu/h)10.5kW(36000Btu/h)12.8kW(44000Btu/h)Remark----AVMCC070EA0AVMCH
V. Installation2. PanelV144) Install the air flow blade.4-1 Fix the right part of the blade to the indoor unit.4-2 Fix the other side of the blade.4
V154x12 Tappedscrew (2)Bolt (4) Air blocking kit (1)Wireless remotecontroller(1)Battery (2)Remote controlholder(1)Owner’sinstructions (1)Owner’sinstru
V. Installation2. PanelV16Tapped screw(6)Fixing bracket(1 or 2)1) Separate the front grille from the panel.1-1 Push the lever of front grille right an
V173) Attach the panel to the indoor unit, then push it to right or left to secure the panel. Narrow side of hole on the panel must be inserted betwee
V. Installation3. Connecting the indoor unit refrigerant pipeV181) Remove the pinch pipe on the pipes and connect theassembly pipes to each pipe, tigh
V19Cutting/Flaring the Pipes1) Make sure that you have the required tools available (pipe cutter, reamer, flaring tool and pipe holder).2) If you wish
V. Installation4. Drain hose installation (Example;4-way cassette type)V20CCCCAAAAUUUUTTTTIIIIOOOONNNNMust fit tightly againstbody without any gap.Dra
V21◆If a concentrated drain hose is installed, refer to the figure below.NNNNooootttteeeeDrain clampAir ventilationConcentrated drain hose1/100 ormore
V. Installation5. Drain pump installation-optional(Example;Low-silhouette duct type)V22K1 K2 K3 K4SW03Drain pumpDrain pump7mmBottom of the drain panFl
V236. Wiring Caution●All wiring and parts shall be the rated ones.●For details of wiring, refer to the circuit diagram attached onto the outdoor unit.
1. Remote controller2. Receiver & display unit (Duct type)3. Transmitter4. Installation2-1. Concealed type2-2. Standard type784-1. Wireles
V. Installation6. WiringV24MCCBELB ELBMCCB MCCBPower supplysinglephase3 phase 3 wireelectrical component boxindoor unit powersupply cablesingle phase
V25●Be sure to run the power supply cable and communication cable through the electrical conduit as shown in the right side figure. ●Select the power
V. Installation6. WiringV26F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIndoor unitWired remotecontroller6-7. Communication
V27(2) Typical wiring error1) Star wiring connection to some of the indoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor un
V. Installation6. WiringV282) Star wiring connection to every indoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIndo
V293) Reverse wiring between indoor and outdoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIndoor unitWired remoteco
V. Installation6. WiringV304) Disconnection between indoor and outdoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIn
V315) Reverse wiring between indoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIndoor unitWired remotecontrollerReve
V. Installation6. WiringV326) Disconnection between indoor unitsF1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2F1F2Outdoor unitIndoor unitWir
V337. Piping and refnet joint selectionAab123456cdehg ijkfH1H2B C D EA, B, C, D, E: Refnet jointLess than 100m of piping length between outdoor unit a
II. Control System1. Remote controllerII21-1. Wireless remote controller(1) 1-way / 4-way cassette / Wall-mounted / Floor standing / Ceiling type1) Co
V. Installation7. Piping and refnet joint selectionV34Refnet joint modelLength (mm)A420420460460B80809090C9.712.822.431.9D--19.228.7E--16.025.6F9.712.
V358. Charge/recovery of refrigerant8-1. Refrigerant charging(1) Outdoor unit is charged with refrigerant when being delivered but additional refriger
V. Installation8. Charge/recovery of refrigerantV368-2. Additional refrigerant amount calculation method (1) The amount of refrigerant filled in the o
V378-3. Recovery of refrigerant(1) Close the service valve of liquid side and then press the refrigerant recovery button on outdoor PCB.(2) When the l
V. Installation9. Testing operationV38 Cautions for operation●Put the power 6 hours before initial operation so that the crank case heater may be heat
V39(7) If Ch displays on the PCB display after tracking, it is the state of compressor not preheated, which means the operation is possible after 2 an
V. Installation10. Cautions for refrigerant leaksV4010-1. IntroductionThe DVM system, like most other air conditioning systems, uses R-22 as its refri
V41(Amount of refrigerant in asingle indoor unit system)Amount of refrigerant withwhich the system is chargedbefore leaving the factory(Additional cha
V. Installation10. Cautions for refrigerant leaksV423) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the small
V43(4) Dealing with situations where the result exceeds the dangerous concentration level.Where the installation of a facility results in a concentrat
II3(2) Duct type1) Cooling only2) Heat pumpOperating mode selection buttonTemperature adjustment buttonsFilter Reset buttonFan speed adjustment button
SAMSUNG DVM Air ConditionerTe chnical ManualDB98-03759A(1)2002.03. DVM E-D/B(cover)-E<03759 3/21/02 6:48 PM Page 1
II. Control System1. Remote controllerII41-2. Wired remote controller(1) 1-way / 4-way cassette / Wall-mounted / Floor standing / Ceiling type1) Cooli
II5(2) Duct type1) Cooling only2) Heat pumpOn/Off & Timer set/cancel buttonOperating indicatorFan speed adjustment buttonFilter Reset buttonTemper
6. Refrigerant system diagram(Cooling only & heat pump)6-1. Refrigerant system diagram6-2. Main parts status73737. Piping and refnetjoint selectio
II. Control System1. Remote controllerII61-3. Centralized controller1-4. Function controllerOperating lampAll On buttonAll Off buttonOn/off indicators
2. Receiver & display unit (Duct type)II72-1. Concealed type(1) Cooling only(2) Heat pumpFilter sign indicatorFan indicatorTimer indicatorRemote c
II. Control System2. Receiver & display unit (Duct type)II82-2. Standard type(1) Cooling only(2) Heat pumpFilter sign indicatorRemote control sens
3. TransmitterII9CN01F1 F2 DVM E-D/B(chapter2)-E<03759 3/21/02 7:32 PM Page 9
II. Control System4. InstallationII104-1. Wireless remote controller(1) Accessories(2) Installation Choose a position where:◆ The signal from the rem
II114-2. Wired remote controller(1) Accessories(2) Installation 1) Open the wired remote controller by using two grooves on its top.2) Secure the rear
II. Control System4. InstallationII12(3) Setting up option switchesIndoor unit PCB1) Adjust K1 DIP switch(SW03) on the PCB to the “OFF” position.2) Tu
II13(4) Example of installing wired remote controllerIndividual controlMeans a wired remote controller controls only 1 indoor unit. In this case, the
II. Control System4. InstallationII144-3. Centralized controller(1) Accessories(2) Wiring diagramEach outdoor unit connected to the same centralized c
II15(4) Assigning addressTurn the arrow of rotary switch on the transmitter to appropriateposition. Transmitters controlled with the same centralized
1. DVM system series2. DVM line-up2-1. Numbering system of model2-2. Combination14201-1. What is DVM?1-2. Features of DVM 1-3. DVM vs VAV 6712IOve
II. Control System4. InstallationII16In Case of Installing wired remote controller together1) Adjust K2 DIP switch(SW03) on the indoor unit PCB to the
II17(6) Example of centralized controller & wired remote controllerInstallation of 1 centralized controller, 4 outdoor units, and 12 indoor units◆
II. Control System4. InstallationII18Level of centralized controller◆ Adjust the DIP switch on the centralized controller PCB,if necessary. Refer to t
II194-4. Function controller(1) Accessories(2) Installation 1) Disassemble the function controller by using a groove on its top.2) Secure the rear cov
II. Control System4. InstallationII20(3) Wiring diagram◆ Install the transmitter, another optional accessory, in the outdoor unit which will be contro
II214-5. Receiver & display unit - Concealed type(1) Accessories(2) Installation 1) Remove the receiver & display unit cover by using the tabo
II. Control System4. InstallationII224-6. Receiver & display unit - Standard type(1) Accessories(2) Installation 1) Remove the receiver & disp
II234-7. Transmitter(1) Accessories(2) Installation ◆ Attach the transmitter to the left side of the electrical component box in outdoor unit, then co
II. Control System4. InstallationII24(3) Wiring diagram◆ Each outdoor unit connected to the same centralized controller has its own transmitter.◆ Dist
5. Assigning addressII255-1. Indoor unit1) Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning s
I6I. Overview1. DVM system series1-1. What is DVM?The DVM(Digital Variable Multi) air conditioning system is operated by a variable-capacity compresso
II. Control System5. Assigning addressII265-2. Outdoor unitYou should display that how many indoor units are connected to the outdoor unit.Refer to th
6. Indoor unit PCB option codeII276-1. PCB option code input method (example : 021E31142285)Be sure to input the option code suitable for the indoor u
II. Control System6. Indoor unit PCB option codeII28Operation method Applicable button Indicating state❋ Step 4 Method)Input the third digit of option
II29Operation method Applicable button Indicating state❋ Step 7 Method)Input the sixth digit by pressingthe Off timer button. example) 021E31142285 Re
II. Control System6. Indoor unit PCB option codeII30Operation method Applicable button Indicating state❋ Step 10 Method)Input the ninth digit by press
II31Operation method Applicable button Indicating state❋ Step 13 Method)Input the 12th digit by pressing theOff timer button. example) 021E31142285Res
II. Control System6. Indoor unit PCB option codeII326-2. Option codeType ModelSEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12RemarkAVMK
II33Type ModelSEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12RemarkAVMHC105E(C)A0AVMHC128E(C)A0AVMHH105E(C)A0AVMHH128E(C)A0AVMWC020E(C)
II. Control System7. S-NetII341) Download S-NET program to your PC, then execute Setup.exe to install the program.2) If the installation is completed
8. Integrating power distribution systemII35 DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 35
I71-2. Features of DVM(1) Customized air conditioner 1) Up to 16 indoor units can be connected to one outdoor unit.2) Indoor units can be combined by
II. Control System9. Building management systemII36 DVM E-D/B(chapter2)-E<03759 3/21/02 7:33 PM Page 36
1. FeaturesIIIIndoor unit1-1. 1-way cassette type1-2. 4-way cassette type1-3. Duct type1-4. Wall-mounted type1-5. Floor standing type1-6. Ceiling ty
III. Indoor unit1. FeaturesIII21-1. 1-Way cassette type (1) Efficient cooling & stylish designThis type sends cool air from the ceiling to one di
III3(3) Features of the 1-way cassette type1) Long-life air filterThe long-life filter requires no maintenance for up to 2,000 hours.2) Bio heat excha
(1) Powerful functionsThe 4-way cassette type air conditioner has all the features of the 1-way cassette type; compact design, long-life air filter, b
III5ItemHLCeiling height2.7~3.5m2.7mSub duct pathway4 Way pattern3 Way patternConventional cooling systemCeiling type cooling systemmax. 750mm ModelA
III. Indoor unit1. FeaturesIII61-3. Duct type (2) High external static pressureAdjustable external static pressure allows ducts from the unit to be u
III7(3) Features of Duct type1) Application methods2) Way of air intake & Inserting air filterAir intake can be positioned either at the back or b
III. Indoor unit1. FeaturesIII81-4. Wall-mounted type (1) BIO-componentsSamsung air conditioners ensure cleaner cooling than any other air conditione
III9 Bio pure filterAmbient atmosphericparticle size rangesRemoval efficiency2) Look at how well these filters perform① Hydrocarbon analysis- Test: A
I8I. Overview1. DVM system series(3) Variable compressor The world’s first PWM(Pulse Width Modulation) compressor controls the cooling & heating c
III. Indoor unit1. FeaturesIII101-5. Floor standing type(1) Features of floor standing type1) The auto shutter increased clean linessThe auto shutter
III115) DesignAir flow blades(up/down orientation)Air flow blades(right/left orientation)Automatic shutterAir outletAir filterAir inletOperation indic
III. Indoor unit1. FeaturesIII121-6. Ceiling type(1) Convenient installationThe ceiling type air conditioner can be easily installed into a corner of
III13(3) Features of ceiling type1) Long life filter with antibacterial treatmentThe detachable filter can be cleaned easily, thus controlling the pro
III. Indoor unit2. SpecificationIII14ModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Heating (Hi
III15ModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rateCo
III. Indoor unit2. SpecificationIII162-2. 4-way cassette type(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeat
III17(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flo
III. Indoor unit2. SpecificationIII182-3. Duct type (Low silhouette)(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHe
III19(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rat
I92) PWM (Pulse Width Modulation) valvePWM valve is the valve to take away the fixed scroll by lifting up through the difference of pressure after the
III. Indoor unit2. SpecificationIII202-4. Duct type (Built-in)(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHea
III21ModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rateCo
III. Indoor unit2. SpecificationIII22(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Hea
III23ModelPower supplyRemarkPerformancePowerOthersSizePanelFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rateCo
III. Indoor unit2. SpecificationIII242-5. Duct type (High pressure)(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHea
III25(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rat
III. Indoor unit2. SpecificationIII262-6. Wall-mounted type(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCool
III27ModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rateCooling
III. Indoor unit2. SpecificationIII28(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating
III29ModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rateCooling
I10I. Overview1. DVM system series(5) Long & single piping system1) Piping can be extended up to 100 meters; refer to the figure.2) The outdoor un
III. Indoor unit2. SpecificationIII302-7. Floor standing type(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCo
III31(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rat
III. Indoor unit2. SpecificationIII322-8. Ceiling type(1) 50HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (
III33(2) 60HzModelPower supplyRemarkPerformancePowerOthersSizeFunction /OptionCoolingHeatingCooling (High/Low)Heating (High/Low)TypeOutputAir flow rat
III. Indoor unit3. Functional parts and safety devicesIII343-1. 1-way cassette type3-2. 4-way cassette typeItem Code NameAVMKC020EA0AVMKH020EA0AVMKC02
III353-3. Duct type (Low silhouette)Item Code NameAVMDC072CA0AVMDH072CA0OSM1304SAC81W135°C90°C103AT (25°C=10kΩ)103AT (25°C=10kΩ)103AT (25°C=10kΩ)0 ~ 4
III. Indoor unit3. Functional parts and safety devicesIII363-4. Duct type (Built-in)3-5. Duct type (High pressure)Item Code NameAVMBC040CA0AVMBH040CA0
III373-6. Wall-mounted typeItem Code NameAVMWC020EA0AVMWH020EA0AVMWC020CA0AVMWH020CA0AVMWC026EA0AVMWH026EA0AVMWC032CA0AVMWH032CA0AVMWC035EA0AVMWH035EA
III. Indoor unit3. Functional parts and safety devicesIII383-7. Floor standing type3-8. Ceiling typeItem Code NameAVMPC060EA0AVMPH060EA0AVMPC060CA0AVM
III394. Capacity tableUnit SizeOutdoor temperature(ºC, DB)14.0TCkW16.0TCkW18.0TCkW19.0TCkW20.0TCkW22.0TCkW24.0TCkW101214161820212325272931333537391012