31English
installation
Preparation
Step 1.1 Choosing the installation
location
Overview of installation location requirements
CAUTION
• Comply with the length and height limits described in
the figure above.
Minimum clearances for the outdoor unit
Wall
Minimum clearance in mm
300
600
Air flow direction
When installing 1 outdoor unit
(6 cases)
(Unit: mm)
2000
300
(Unit : m)
Model
Pipe length Pipe height
Minimum Maximum Maximum
09/12 3 15 7
18/24 3 20 12
100 mm or more
Drain hose hole
You can select the direction of
draining (left or right).
Maximum pipe height: 7 /12 m
Maximum pipe length: 15/20 m
Make at least one round to
reduce noise and vibration.
The actual units may look different from
the images depicted here.
Make a U-trap (A) on the
pipe (which is connected
to the indoor unit) at outer
wall and cut the bottom
part of the insulation
(about 10 mm) to prevent
rainwater from getting
inside through the
insulation.
Outdoor Unit
Outer wall
Indoor
Unit
Cut insulation to have
rainwater drained
Top view
Side view
125 mm
or more
125 mm
or more