9ENGLISHIndoor Unit Installation4Screw eight nuts to the suspension bolts making space for hanging theindoor unit. You must install the suspe
10Purging the Unit Gas refrigerant portLiquid refrigerant portg The designs and shape are subject to change according to the model.From factory the
11ENGLISHND0561/0711 Air outletConnecting the Refrigerant PipeThere are two refrigerant pipes of differing diameters: A smaller one for the l
12Cutting/Flaring the Pipes1Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder)2If you want to shorte
13ENGLISHPerforming Leak Test & Insulationg The designs and shape are subject to change according to the model.Leak checkLEAK TEST WITH NITROGEN
14Performing Leak Test & Insulation (Continued) 5Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe re
15ENGLISH Drain pipe and Drain Hose InstallationInsulation drainpipeBandBandFlexible hoseDrain hose portDrainpipeAdhesivesInsulation cover bandInsula
16Drain pipe Connection 1The drain pipe should be installed within 100mm(3.94") from the flexible hose, lift up from 100mm(3.94") to 550mm(2
17ENGLISHTesting the DrainageYou should test drainage after completing the installation. Prepare a little water about 1.0 liter.1Open the cover water
18Wiring WorkSilver solderN LN L N L N LIndoor Unit 1Outdoor UnitIndoor Unit 2 Indoor Unit 3Wired Remote Control208-230V~h ELB : Essential Installati
Air Conditionerinstallation manualimagine the possibilitiesThank you for purchasing this Samsung product.Cassette Type SeriesSlim 1 Way cassetteDB68-0
19ENGLISHWiring Workh Rating currentUnit ModelRating currentAMFN1DCH0070090120.23 A0.25 A0.28 ASpecification of electronic wirePower s
20Wiring Work (Continued) Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and
21ENGLISHSetting an indoor unit address and installation optionSet the indoor unit address and installation option with remote controller option. Set
22Setting an indoor unit address and installation option (Continued)Option setting Status1. Setting SEG2, SEG3 optionPress Low Fan button(∨) to enter
23ENGLISHSetting an indoor unit address and installation option (Continued)Option setting Status12. Setting Cool mode Press Mode button to be change
24Setting an indoor unit address and installation option (Continued)1.Check whether power is supplied or not. - When the indoor unit is not plugged i
25ENGLISHSetting an indoor unit address and installation option (Continued)1.Check whether power is supplied or not. - When the indoor unit is not pl
26Setting an indoor unit address and installation option (Continued)Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX 02 series installation option(Detailed)
27ENGLISHSetting an indoor unit address and installation option (Continued)Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24Explanation PAGEIndividual contr
28Setting an indoor unit address and installation option (Continued)(*5) This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only
2Contents Safety Precautions ... 3 Accessories ...
29ENGLISHSetting an indoor unit address and installation option (Continued)Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX 05 series installation option(De
30Setting an indoor unit address and installation option (Continued)1) Height dierence : The dierence of the height between the corresponding ind
31ENGLISHChanging a particular option Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODEThe option mode you want to changeThe tens’ digit of a
32Wireless Remote Control-Buttons and DisplayFinal Checks and User TipsTo complete the installation, perform the following checks and tests to ensure
33ENGLISHTroubleshooting If an error occurs during the operation, an LED flickers and the operation is stopped except the LED. If you re-operate t
34 If you turn off the air conditioner when the LED is flickering, the LED is also turned off. If you re-operate the air conditioner, it operates no
35ENGLISH MEMODVMS_1Way Cassette_IM_EN_03806A-02.indd 35 2014-07-07 오전 11:07:53
3ENGLISH(Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.)WARNING• Always disconnect
4 Make sure that you earth the cables.- Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing i
5ENGLISHAccessoriesSelecting the Installation LocationThe following accessories are supplied with the indoor unit. The type and quantity may differ de
6Selecting the Installation Location (Continued)Space Requirements for Indoor Unit1500(59) or more1500(59) or more1500(59) or more1500(59) or moreUnit
7ENGLISHSelecting the Installation Location (Continued)No. Name DescriptionLiquid pipe connection ø6.35(1/4")Gas pipe connection ø12.70(1/2&quo
8ConcreteSuspension bolt(ø9.52(3/8") or M10)Hole in anchorHole in plugInsertCeiling supportIt is recommended to install the Y-joint before instal