E-2ContentsSafety Precautions ... 3Accessories ...
E-11Selecting the Installation Location (Continued)AVXCMUnit : mmNo. Name DescriptionLiquid pipe connectionø6.35 (1/4")Gas pipe connectionø12
E-12Indoor Unit InstallationConcreteSuspension bolt(3/8" or M10)Hole in anchorHole in plugInsertIt is recommended to install the Y-joint before i
E-13Indoor Unit Installation4Screw eight nuts to the suspension bolts making space for hanging theindoor unit. CAUTION You must insta
E-14Purging the Unit Gas refrigerant portLiquid refrigerant port The designs and shape are subject to change according to the model.From factory the
E-15Connecting the Refrigerant PipeRefrigerant oilTorque wrenchFlare nutUnionSpannerThere are two refrigerant pipes of differing diameters: A sma
E-16Cutting/Flaring the Pipes1Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder)2If you want to shor
E-17Performing Leak Test & Insulation The designs and shape are subject to change according to the model.Leak checkLEAK TEST WITH NITROGEN (befo
E-18Performing Leak Test & Insulation (Continued) 5Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe
E-19 Drain pipe and Drain Hose InstallationInsulation drainpipeBandBandFlexible hoseDrain hose portDrainpipeAdhesivesInsulation cover bandInsulation
E-20Drain pipe and Drain Hose Installation (Continued)Drainpipe Connection 1The drain pipe should be installed within 100mm from the flexible hose, l
E-3Safety Precautions(Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.) WARNING•
E-21Drain pipe and Drain Hose Installation (Continued)Centralized Drainage 1Install main air vent at the front of the farthest indoor unit from the ma
E-22Wiring WorkSilver solderN LN LN LN LELCBMCCB+ELBIndoor Unit 1Outdoor UnitIndoor Unit 2 Indoor Unit 3Wired Remote Control220-240V~ ELCB : Essenti
E-23Wiring WorkRating currentUnit Model Rating currentAVXC10220280360.18A0.20A0.23AAVXCS0220280360.20A0.23A0.25AAVXC2
E-24Wiring Work (Continued) Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local a
E-25Indoor Unit Setting1 Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.2 The
E-26Additional FunctionsK5 K6 K7 K8K1 K2 K3 K4K9K10K11K12No. Function ON OFFSW07K9Indoor Expansion Valve For Heating Stop Fix 80 step 0 or 80 stepK10
E-27Final Checks and User TipsTo complete the installation, perform the following checks and tests to ensure that the air conditioner operates correct
E-28Troubleshooting LED DisplayLED Display on the receiver & display unit Abnormal conditionsIndicatorsOperatingGreen RedPower resetX X X
E-29Troubleshooting LED Display Abnormal conditionsIndicatorsOperatingGreen Red Self-diagnostic error (including the indoor unit not detected)
"EEE Yönetmeliğine Uygundur" "This EEE is compliant with RoHS"AVXC1@@_IM_E_29824-2_12.14.09.indd 30 2009-12-14 17:39:37
E-4 Make sure that you earth the cables. - Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthin
INSTALLATION MANUALCassette Type Series1 way cassette : AVXC1AVXCS(Slim)2 way cassette : AVXC24 way cassette : AVXC4 AVXCM(mini)DB98-317
E-5AccessoriesThe following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications.AVXC1/AV
E-6Indoor Unit There must be no obstacles near the air inlet and outlet. Install the indoor unit on a ceiling that can support its weight. Ma
E-7Selecting the Installation LocationDimension of the indoor unitAVXC1Unit : mm No. Name DescriptionLiquid pipe connectionø6.35 (1/4”)Gas pipe
E-8Selecting the Installation Location (Continued)Dimension of the indoor unitUnit : mmNo. Name DescriptionLiquid pipe connection ø6.35 (1/4”)Gas pi
E-9Selecting the Installation Location (Continued)AVXC2Unit : mm 890919103011725230136.549318015772.5650575No. Name DescriptionLiquid pipe connect
E-10Selecting the Installation Location (Continued)No. Name DescriptionLiquid pipe connection045/056ø6.35 (1/4”)071/090/112/128/140ø9.52 (3