29
ENGLISH
Setting option switches and function of keys
Field setting mode
Field Setting Value(FSV) Table
• Reset the power after changing the Field Setting Value.
NOTE
• Code 10✴✴ : Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out,
Room), Cooling(Water Out, Room), DHW(Tank)
• Code 20✴✴ : Water law design and external room thermostat Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor &
FCU), WL & Thermostat types
Field Setting Value
Main Menu &
Code
Sub Menu Function Description Sub Code Default Min Max Step Unit
Remote
Controller
Setting Range
Code 10✴✴
Water Out Temp for Cooling
Max ✴✴11 25 18 25 1 ˚C
Min ✴✴12 16 5 18 1 ˚C
Room Temp for Cooling
Max ✴✴21 30 24 30 1 ˚C
Min ✴✴22 18 18 22 1 ˚C
Water Out Temp for Heating
Max ✴✴31 55 37 55 1 ˚C
Min ✴✴32 25 15 37 1 ˚C
Room Temp for heating
Max ✴✴41 30 24 30 1 ˚C
Min ✴✴42 16 16 22 1 ˚C
DHW Tank Temp
Max ✴✴51 50 50 70 1 ˚C
Min ✴✴52 40 30 40 1 ˚C
Water Law Code
20✴✴
Outdoor Temp for Water Law (Heating)
Point ①
✴✴11 -10 -20 5 1 ˚C
Point ②
✴✴12 15 10 20 1 ˚C
Water Out Temp for WL1 Heating
(WL1-Floor)
Point ①
✴✴21 40 40 55 1 ˚C
Point ②
✴✴22 25 17 37 1 ˚C
Water Out Temp for WL2 Heating (WL2-
Fan Coil Unit)
Point ①
✴✴31 50 40 55 1 ˚C
Point ②
✴✴32 35 17 37 1 ˚C
Heating Water Law for Auto Mode WL Type ✴✴41 1(WL1) 1 2(WL2) - -
Outdoor Temp for Water Law (Cooling)
Point ①
✴✴51 30 25 35 1 ˚C
Point ②
✴✴52 40 35 45 1 ˚C
Water Out Temp for WL1 Cooling
(WL1-Floor)
Point ①
✴✴61 25 18 25 1 ˚C
Point ②
✴✴62 18 5 18 1 ˚C
Water Out Temp for WL2 Cooling (WL2-
Fan Coil Unit)
Point ①
✴✴71 18 18 25 1 ˚C
Point ②
✴✴72 5 5 18 1 ˚C
Cooling Water Law WL Type ✴✴81 1(WL1) 1 2(WL2) - -
External Thermostat Application
#1(Floor) ✴✴91 0(No) 0 1(Yes) - -
#2(FCU) ✴✴92 0(No) 0 1(Yes) - -
EHS Control unit_MIM-E03@_IM_E_34413-2.indd 29 2012-03-08 오후 5:55:24