7
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
If you choose to select outdoor unit combination other than the ones in following table, total capacity of the
connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity. 0.5 × Σ(Outdoor unit
capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ(Outdoor unit capacity)
Model name for combination
AM080FXVC AM100FXVC AM120FXVC AM140FXVC AM160FXVC AM180HXVC
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz
Rated capacity
Cooling (kW)
22.4 22.5 28.0 28.2 33.6 33.6 40.0 40.0 45.0 45.0 50.4 50.5
Heating (kW)
25.2 25.2 31.5 31.5 37.8 37.8 45.0 45.0 50.4 50.0 56.7 56.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
11.2 11.3 14.0 14.1 16.8 16.8 20.0 20.0 22.5 22.5 25.2 25.3
Maximum (kW)
29.1 29.3 36.4 36.7 43.7 43.7 52.0 52.0 58.5 58.5 65.5 65.7
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080FXVC
1
AM100FXVC
1
AM120FXVC
1
AM140FXVC
1
AM160FXVC
1
AM180HXVC
1
AM200HXVC
AM220KXVJ
AM240KXVJ
Maximum number of connectable
indoor units
14 18 22 26 29 33
Model name for combination
AM200HXVC AM220KXVJ AM240KXVJ AM260KXVJ AM280KXVJ AM300KXVJ
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz
Rated capacity
Cooling (kW)
56.0 56.0 61.6 62.0 67.2 67.5 73.0 73.2 78.4 78.7 84.0 84.2
Heating (kW)
63.0 63.0 69.3 69.3 75.6 75.6 81.9 81.5 88.2 88.2 94.5 94.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
28.0 28.0 30.8 31.0 33.6 33.8 36.5 36.6 39.2 39.4 42.0 42.1
Maximum (kW)
72.8 72.8 80.1 80.6 87.4 87.8 94.9 95.2 101.9 102.3 109.2 109.5
Number of individual outdoor units
1 1 1 2 2 2
Combined
outdoor unit
AM080FXVC
AM100FXVC
1 1 1
AM120FXVC
AM140FXVC
AM160FXVC
1
AM180HXVC
1
AM200HXVC
1 1
AM220KXVJ
1
AM240KXVJ
1
Maximum number of connectable
indoor units
36 40 44 47 51 55
DVM S DESERT_IM_DB68-05121A-06_EN.indd 7 2018-03-16 오후 4:33:52