AMFXMDCH SeriesAir Conditionerinstallation manualimagine the possibilitiesThank you for purchasing this Samsung product.DVM S Eco_IM_03408A-05_EN.i
10Installation locationMoving the Outdoor Unit Select the moving route in advance. Be sure that moving route is safe from the weight of the outdoo
11ENGLISHBase ground work< When installing on the ground >Drain hole150mm (6inch) or more< When installing on the roof >Install the outdo
12Refrigerant pipe installationRefrigerant pipe work The length of refrigerant pipe should be as short as possible and the height dierence between
13ENGLISHSelecting refrigerant pipe Temper grade and minimum thickness of the refrigerant pipeOuter diameter [mm (inch)] Minimum thickness [mm (inch)]
14Refrigerant pipe installationSelecting Y-joint Select the rst Y-joint according to main pipe size of each outdoor unit capacity. Select the oth
15ENGLISHDirection of the pipe when brazing Brazing the pipe should be done with the pipe headed downward or horizontally. Avoid brazing with the
16Refrigerant pipe installationTightening are connection area Check that the aring is properly made. Align the center of the piping and sucien
17ENGLISHPipe installation for an outdoor unitPipe directionThe refrigerant pipe can be pulled out from front, ank, rear, and bottom side, so install
18Refrigerant pipe installationRefrigerant pipe installation examplesUsing a Y-joint Using a Y-joint/EEV kitUsing a header joint Using a header joint/
19ENGLISHClassication Y-joint connection Y-joint / EEV kit connectionMaximum allowable length of pipeOutdoor unit ~ Indoor unitsActual LengthThe dist
2ContentsSafety precautions ... 3Outdoor unit ty
20Refrigerant pipe installationConnection by header jointgOutdoor unitHeader jointIndoor unitConnection by Y-joint/header jointH2H1f cg Outdoor unitIn
21ENGLISHRefrigerant pipe workRefrigerant Y-joint installation Install the Y-joint ‘horizontally’ or ‘vertically’. Install horizontally Install
22Refrigerant pipe installationCorrect use (The insertion depth of connecting pipe)Incorrect use(The insertion depth of connecting pipe)Basic specica
23ENGLISH• When using A~J type of header joint, connect the header joint to the pipe with provided reducer. • When using K~Z type of header joint, c
24Refrigerant pipe installationPerforming air tightening test Use tools for R410A only to prevent the inow of foreign substances and to resist the
25ENGLISHVacuuming a pipe and an indoor unit Use the tools for R410A only to prevent the inow of foreign substances and resist against the internal
26Refrigerant pipe installationSelecting additional refrigerant charging Basic refrigerantThe basic amount of additional refrigerant charged at a fa
27ENGLISH[Unit: kg(lb)]Capacity(kBtu)Model6 7.5 9 9.5 12 15 18 20 24 27 30 36 48 54Ceiling (AMFNCDC/AA, AMJNCDC/AA)0.39 (0.86)0.39 (0.86)0.56
28Refrigerant pipe installationInsulating refrigerant pipe or Y-joint You must check if there is a gas leak before completing all the installation p
29ENGLISHInsulating refrigerant pipe You must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area. If you insulate the pipe
3ENGLISHSafety precautions WARNINGState of California Proposition 65 Warning (US only)This product contains chemicals known to the State of California
30Refrigerant pipe installationInsulating the header joint Fasten the header joint using a cable tie and cover the connected part. Insulate the he
31ENGLISHWiring work Wiring work should be performed in accordance with related laws such as ‘Technical specication on electric installation’, ‘Wir
32Wiring workOverall System CongurationConnection of the power cable (1 phase 2 wires)Distribution board Outdoor unit Indoor unitCommunication cable2
33ENGLISH• You must install an earth leakage breaker. - ELCB(Earth Leakage Circuit Breaker) - MCCB(Molded Case Circuit Breaker) - ELB(Earth Leakage f
34Wiring workSelecting compressed ring terminal Select a compressed ring terminal of a connecting power cable based on a nominal dimensions for cabl
35ENGLISHInstalling grounding wire Grounding must be done by a qualied installer for your safety. Use the grounding wire by referring to the spec
36Grounding workIf the power distribution circuit does not have a grounding or the grounding does not comply with specications, a ground rod must be
37ENGLISHSetting outdoor unit option switch and key functionPBA shape7-SEGMENT (DISPLAY)DIP S/W (K5~K16)Do not connect wires to these terminal blocksT
38Setting outdoor unit option switch and key functionS/W functionTact switchHeating KEY operation Cooling KEY operation Reset View ModeK1 K2 K3 K4DIP
39ENGLISH K4 input display order(1)Current frequency (2)Low pressure value (3)Outdoor temperature (4)Discharge temperature (5)OLP temp
4Safety precautionsInstalling the unitIMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the electrical
40Setting outdoor unit option switch and key function K9, K10: Silent mode option. This reduces FAM RPM to operate the outdoor unit quietly during n
41ENGLISH K15, K16: Changing defrost option tableSwitchFunctionK15 K16ON ON MIDON OFF MIDOFF ON LOW1OFF OFF LOW2 Defrost mode will start when the
42Setting outdoor unit option switch and key function4) After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited
43ENGLISHHow to put the refrigerant into the refrigerant container before pump down operation When the amount of refrigerant charged in the system e
44Checking lists after nishing installation Before supplying power, measure the power terminal (L, N) and outdoor unit grounding using insulation-r
45ENGLISHInspection and check operationPrecautions before check operation• When the outdoor temperature is low, turn on the main power 3 hours before
46Inspection and check operationCheck operation1) Use KEY MODE to run check operation. - When the check operation is not completed, UP (unprepared) w
47ENGLISHAutomatic refrigerant amount detection function (Checking th amount of refrigerant)This function detects amount of refrigerant in the system
48Trial operation Check the power supply between the outdoor unit and the cabinet panel. - 1 phase power supply : L, N Check the indoor unit. - C
49ENGLISHMemoDVM S Eco_IM_03408A-05_EN.indd 49 2016-11-11 오후 1:28:01
5ENGLISHOutdoor unit type ShapeModel Cooling and Heating 1phaseAM036FXMDCHAM048FXMDCHAM053FXMDCHInstallation combination You must install the ind
DB68-03408A-05DVM S Eco_IM_03408A-05_EN.indd 50 2016-11-11 오후 1:28:01
6Deciding to where to install the outdoor unitDecide the installation location based on the following condition and obtain the user’s approval. Avo
7ENGLISH• Install the indoor unit away from any interfering sources such as radio, computer, stereo equipment and also select a place where the elect
8Installation location Make a space for ventilation and service as seen in the picture. When multiple outdoor units are combined for installation,
9ENGLISHWhen installing more than 1 outdoor unitUnit: mm (inch) When 3 sides of the outdoor unit are blocked by the wall300 (12) or more300 (12) or