X Ratings shown are net capacities.
X Capacities are based on following conditions;
- Equivalent refrigerant piping length : 5m / Level difference : 0m.
;
Note
MSP(Middle static pressure) duct
5
5-2. Capacity tables
1) RC052DHXEA+NS052SDXEA
2) RC071DHXEA+NS071SDXEA
(1) Cooling
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 21 35 43 50
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20 7.65 5.36 1.75 7.64 5.35 1.96 6.6 4.62 2.05 5.70 3.99 4.5 3.90 2.73 3.72
16 22 7.84 5.49 1.79 7.83 5.48 2.01 6.76 4.73 2.11 5.84 4.09 4.61 4.00 2.80 3.81
18 25 8.03 5.62 1.83 8.02 5.62 2.06 6.93 4.85 2.16 5.98 4.19 4.72 4.10 2.87 3.90
19 27 8.23 5.76 1.88 8.22 5.75 2.11 7.10 4.97 2.21 6.13 4.29 4.84 4.20 2.94 4.00
22 30 8.43 5.90 1.93 8.42 5.89 2.16 7.27 5.09 2.26 6.28 4.39 4.96 4.30 3.01 4.10
24 32 8.63 6.04 1.97 8.62 6.03 2.21 7.44 5.21 2.32 6.43 4.50 5.08 4.40 3.08 4.19
(2) Heating
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-20 -10 7 24
DB TC PI TC PI TC PI TC PI
16 5.77 2.85 6.9 2.62 8.16 2.26 8.63 2.33
18 5.72 2.82 6.83 2.60 8.08 2.24 8.54 2.30
20 5.66 2.79 6.76 2.57 8.00 2.22 8.46 2.28
21 5.60 2.76 6.69 2.54 7.92 2.20 8.38 2.26
22 5.55 2.73 6.63 2.52 7.84 2.18 8.29 2.23
24 5.49 2.71 6.56 2.49 7.76 2.15 8.21 2.21
(1) Cooling
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-10 21 35 46
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20 5.22 3.91 1.32
5.41 4.06 1.47
4.65 3.49 1.45 3.72 2.79 2.18
16 22 5.34 4.01 1.35
5.54 4.16 1.51
4.76 3.57 1.49 3.81 2.86 2.24
18 25 5.48 4.11 1.39
5.68 4.26 1.54
4.88 3.66 1.52 3.90 2.93 2.29
19 27 5.61 4.21 1.42
5.82 4.37 1.58
5.00 3.75 1.56 4.00 3.00 2.35
22 30 5.74 4.31 1.45
5.96 4.47 1.62
5.12 3.84 1.60 4.10 3.07 2.41
24 32 5.88 4.41 1.49
6.10 4.58 1.66 5.24 3.93 1.64
4.19 3.15 2.46
(2) Heating
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 7 24
DB TC PI TC PI TC PI TC PI
16 4.39 2.05 5.30 2.17 6.12 1.80 6.32 1.94
18 4.34 2.03 5.25 2.15 6.06 1.78 6.26 1.92
20 4.30 2.01 5.20 2.13 6.00 1.76 6.20 1.90
21 4.26 1.99 5.15 2.11 5.94 1.74 6.14 1.88
22 4.21 1.97 5.10 2.09 5.88 1.72 6.08 1.86
24 4.17 1.95 5.05 2.07 5.82 1.71 6.02 1.84
Page view 97