Hardware Installation Guide
revision 88 — 221
43. Installation
To install the Star Multiplexer, perform the installation procedures described in the following sections, in the
order in which they are presented.
43.1. Wiring
1. Wire the upstream host communication.
2. Wire the downstream device communication.
3. Wire the power input.
43.1.1 Upstream Controller Communication
The Star Multiplexer can communicate to the Intelligent System Controller by one of four downstream
ports, either by RS-485 (2-wire) communications or RS-232 to RS-485 converters. The recommended
configuration is with RS-485 (2-wire) communications.
Each port of the Intelligent System Controller (ports 2-5) can support up to four (4) Star Multiplexers within
1000 feet of the Intelligent System Controller. The Intelligent System Controller ports are not limited to only
the Star Multiplexer. The controller is capable of other addressable devices (such as the Input Control
Module, Output Control Module, Single Reader Interface Module, or Dual Reader Interface Module) on the
same port as the Star Multiplexer. However, the same distance limitation applies.
Upstream Host Communication Wiring
The RS-232 communications interface is for short distance wiring or point to point communications. This
interface is intended for a short distance communication because its high impedance is more susceptible to
noise. Cable length is generally limited to 50 feet (15m). If required, this distance may be extended to a few
hundred feet by using low capacitance shielded cables (the optimal cable is a Belden 9610 or equivalent
wire) or line signal converters.
RS-232 2-WIRE
RxDTxD
TR+
TXD
TR-
RXD
GND
RS-485 2-WIRE
TR+
TXD
TR-
RXD
GND
GND TR-TR+