Air Conditionerinstallation manualimagine the possibilitiesThank you for purchasing this Samsung product.Cassette Type Series1 Way cassette : AMFN
10Selecting the Installation LocationUnit : mmAMFN4DEH/AMKN4FEHAB890~910 (Celling opening)950735 (Suspension position)890~910 (Celling opening
11Indoor Unit InstallationConcreteSuspension bolt(ø9.52 or M10)Hole in anchorHole in plugInsertCeiling supportIt is recommended to install the Y- join
126Adjust the height of the indoor unit by using jigs. You should adjust the jigs and the pattern sheet to fit the cutting dimensions of ceiling.
13Connecting the Refrigerant PipeThere are two refrigerant pipes of differing diameters: A smaller one for the liquid refrigerant A larger o
14Cutting/Flaring the Pipes1Make sure that you prepared the required tools. (pipe cutter, reamer, flaring tool and pipe holder)2If you want to shorte
15Outer diameter (D, mm)Connection TorqueFlare dimension (A, mm)Flare shape (mm)kgf•cm N•m6.35 140~180 14~18 8.70~ 9.109.52 350~430 34~42 12.80~ 13.20
16Performing Leak Test & Insulation (Continued) 5Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe re
17 Drain pipe and Drain Hose InstallationInsulation drainpipeBandBandFlexible hoseDrain hose portDrainpipeAdhesivesInsulation cover bandInsulation co
18Drainpipe Connection 1The drain pipe should be installed within 100mm from the flexible hose, lift up from 100mm to 550mm and lift down 20mm or mor
19Centralized Drainage 1Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3
2Contents Safety Precautions ... 2 Accessories ...
20Silver solderN LN L N L N LIndoor Unit 1Outdoor UnitIndoor Unit 2 Indoor Unit 3Wired Remote Control220-240V~h ELB : Essential InstallationEEV kitIn
21Wiring Workh Rating currentUnit ModelRating currentAMFN1DEH0220280360.200.230.25AMHN1DEH0170220.140.15AMJN1DEH056
22 Select the power cable in accordance with relevant local and national regulations. Wire size must comply with local and national code. Power
231Prepare the following tools.Tools Crimping pliersConnection sleeve (mm)Insulation tapeContraction tube (mm)Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ
24Wiring Work (Continued)5Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape. A to
25Setting an indoor unit address and installation optionSet the indoor unit address and installation option with remote controller option. Set the eac
26Option setting Status1. Setting SEG2, SEG3 optionPress Low Fan button(∨) to enter SEG2 value.Press High Fan button(∧) to enter SEG3 value.Each time
27Setting an indoor unit address and installation option (Continued)Option setting Status12. Setting Cool mode Press Mode button to be change to Cool
281.Check whether power is supplied or not. - When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.2.
29Setting an indoor unit address and installation option (Continued)1.Check whether power is supplied or not. - When the indoor unit is not plugged i
3installinG the unitIMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always d
30Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX 02 series installation option(Detailed)Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODE Use of
31Setting an indoor unit address and installation option (Continued)* Advanced function: Controlling cooling/heating current or power saving with mot
32Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX 05 series installation option(Detailed)Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODEUse of A
33(*1) Height dierence : The dierence of the height between the corresponding indoor unit and the indoor unit installed at the lowest place. For
34SEG 3, 4, 5, 6, 8, 9 additional informationWhen the SEG 3 is set as "1" and follow Auto Change Over for HR only operation, it will operat
35Changing a particular option Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODEThe option mode you want to changeThe tens’ digit of an optio
36Final Checks and User TipsTo complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly
37Troubleshooting 1 Way cassette / 2 Way cassette If an error occurs during the operation, an LED flickers and the operation is stopped except the
38Troubleshooting(Continued) 1 Way cassette / 2 Way cassette(Continued)Abnormal condition Error codeLED DisplayOperation Defrost Timer FilterError on
39Troubleshooting(Continued)Abnormal condition Error codeLED DisplayOperation Defrost Timer Filter1. When there is no communication between the indoo
4AccessoriesSelecting the Installation LocationThe following accessories are supplied with the indoor unit. The type and quantity may differ depending
This product is RoHS compliantDVM S CASSETTE_IM_03565A-09_EN.indd 40 2017-06-07 오전 8:59:07
5Selecting the Installation Location (Continued)Space Requirements for Indoor Unit AMFN1DEH/AMHN1DEH/AMJN1DEH / AMFN2DEH
6Selecting the Installation Location (Continued)Insulation Guide Indoor unit A B C D E2Way-Cst5.2~7.2kw (890x230x575)880x185 880x185 570x185 570x185 8
7Selecting the Installation Location (Continued)Dimension of the indoor unitNo. Name DescriptionLiquid pipe connection ø6.35Gas pipe connection ø12.
8Selecting the Installation Location (Continued)Unit : mmDimension of the indoor unitNo. Name DescriptionLiquid pipe connectionAM056JN1 : ø6.35 (
9Selecting the Installation Location (Continued)No. Name DescriptionLiquid pipe connection056 : ø6.35071 : ø9.52Gas pipe connection056 :