Samsung AQN36VFUAGM User Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 45
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
28
Fixing the installation plate
Wall
<0.79inch
(20mm)
Plastic
Anchor
2. Fix the indoor unit.
If you x the indoor unit on a wall
(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.
If you x the indoor unit on a window frame
(1) Determine the positions of the wooden uprights to be
attached to the window frame.
(2) Attach the wooden uprights to the window frame giving
attention to the weight of the indoor unit.
(3) Attach the installation plate to the wooden upright using
tapping screws.
If you x the indoor unit on a gypsum board
(1) Use studnder tond out locations of the studs.
(2) Fix the plate hanger on two studs.
• Ifyoumounttheplatetoaconcretewallusingplasticanchors,makesurethat
gapsbetweenthewallandtheplate,createdbyprojectedanchor,islessthan
0.79inch(20mm).
• Searchforotherspotsiftherearelessthantwostuds,orthedistancebetweenthestudsaredierentfromthe
plate hanger.
• Fixtheinstallationplatewithoutincliningtooneside.
• Makesurethatawallcanwithstandtheweightoftheproduct.Ifyouinstalltheproductinaplacewhereitisnot
strongenoughtowithstandtheproductweight,theunitcouldfallandcauseinjury.
Connecting the assembly cable
• Connectthepowercabletotheauxiliarycircuitbreaker.Ifeverypolefailstoconnecttothe
powersupply,itmustbeincorporatedinawirewithacontactopeningof≥0.118inch(3mm).
Cable specication
Connecting the cable
Electrical work
(1)Forelectricalandearthworks,complywiththe‘technicalstandardsofelectricalinstallationsandthethe‘wiring
regulations’oftheElectricityEnterprisesAct.
(2)Tightentheterminalblockscrewto0.89~1.33lb•ft[1.2~1.8N•m(12~18kgf•cm)].
(3)Precautionswhenconnectingterminalblocksoftheindoorunit
Beforeconnecting,makesuretheconnectingpartoftheterminalsocketisfacingupwards.
Upside down
The terminal
socketisdamaged.
There is no ring
terminalto cover the wire.
Model Use AWG Cross sectional area (mm
2
)
09/12/18/24
Mainpowersupply3-wirePowercable 13 or fewer 2.5 or more
Indoorpowersupply3-wirepowercable 15 or fewer 1.5 or more
2-wireassemblycable 15 or fewer 1.5 or more
36
Mainpowersupply3-wirePowercable 10 or fewer 4ormore
Indoorpowersupply3-wirepowercable 15 or fewer 1.5 or more
2-wireassemblycable 15 or fewer 1.5 or more
Vivaldi MAX_AQN09VFU@@ IB&IM_32163A-3_EN.indd 28 2015/8/17 17:25:40