Performing leak tests
Insulation
No gap
NBR(T13.0 or thicker)
B
A
The designs and shape are subject to
change according to the model.
LEAK TEST WITH NITROGEN (before opening valves)
In order to detect basic refrigerant leaks, before recreating the vacuum
and recirculating the R22, it’s responsable of installer to pressurize the whole
system with nitrogen (using a cylinder with pressure reducer) at a pressure
above 30 bar (gauge).
LEAK TEST WITH R22 (after opening valves)
Before opening valves, discharge all the nitrogen into the system and create
vacuum. After opening valves check leaks using a leak detector for
refrigerant R22.
Once you have completed all the connections, check for possible leaks using
leak detector specifically designed for HFC refrigerants.
To check for gas leaks on the... Then, using a leak detector,
check the...
Outdoor unit Valves on sections A and B.
Once you have checked that there are no leaks in the system, you can insulate
the piping and hose.
1
To avoid condensation problems, place an insulator around each
refrigerant pipe.
Note When insulate the pipe, be sure to overlap the insulation.
You have to use more than 120°C insulation(T13.0 or thicker
Acrylonitrile Butadien Rubber) for the gas refrigerant pipe.